(Solved): A three-phase synchronous generator is connected to an infinite bus through a transmission line The ...
A three-phase synchronous generator is connected to an infinite bus through a transmission line The inductive reactance of the transmission line is 1Ω, and the synchronous reactance of the machine is 2Ω. The line-to-line internal e.m.f. is 20kV and the generator delivers 50MW of real power to the infinite bus. Taking the infinite bus as the reference for the angles, the power angle is 30∘. Compute the following: a) The line-to-line voltage magnitude of the infinite bus. b) The line-to-line voltage at the terminals of the generator c) The reactive power consumed by the transmission line d) Can the active power output of this generator be increased to 120MW without adjusting the field current?
To solve the given problem, we'll use the per-unit system and perform calculations based on the given data. We'll assume a base value of 100 MVA for the generator.